Monitoring of Cooling Tower Water 

Cooling towers cools the warm water by direct contact between atmospheric air and the water. This process allows airborne contaminants, organic matters and particles to become deposited into the cooling water. This, combined with the contaminants in the feed water, creates an environment for microorganism growth, solid deposits and scaling. If Legionella bacteria is present in the system, there is a risk to spread the Legionnaires' disease (退伍軍人病) to human via the air conditioning system. Therefore, cooling tower water quality must be monitored in a regular basis to prevent destroying of the system and spreading of diseases to users.

Code of Practice in Hong Kong

In Hong Kong, Code of Practice for Water-cooled Air Conditioning Systems has been published by the Electrical and Mechanical Services Department (EMSD), HKSAR Government. According to the practice, the following parameters should be monitored regularly to ensure the cooling tower water meets the requirements: 

Parameter

Cooling Water Quality Criteria (Fresh Water Typed Tower)

Minimum Monitoring Frequency

Heterotrophic colony count (HPC)

Less than 100,000 cfu/mL

Monthly

Legionella bacteria count

Less than 10 cfu/mL

Monthly / Quarterly

Conductivity

Less than 1500 μS/cm

Monthly

Total dissolved solids

Less than 1500 mg/L 

Monthly 

Suspended solids

Less than 180 mg/L 

Monthly 

Calcium hardness

Less than 500 mg/L

Monthly

pH

8 – 10 

Monthly

Total alkalinity

80 – 500 mg/L

Quarterly 

Chloride as mg/L Cl

Less than 200 mg/L

Quarterly

Sulphate as mg/L SO4

Less than 200 mg/L

Quarterly

Total iron as mg/L Fe

Less than 1.0 mg/L

Quarterly

Total Residual Chlorine

Less than 0.3 mg/L

Monthly

Biochemical Oxygen Demand (BOD5)

Refer to EPD’s Technical Memorandum on Standards for Effluent Discharged into Drainage and Sewerage Systems, Inland and Costal Waters

Monthly

Chemical Oxygen Demand (COD)

Ref: Code of Practice for Water-cooled Air Conditioning Systems Part 2: Operation and Maintenance of Cooling Towers (EMSD, HKSAR, Jan 2007)

Why choose Enviro Labs?

Enviro Labs holds HOKLAS accreditation* for all the above parameters. 

We provide high quality of testing services at reasonable price. 

All the analyses are conducted according to the international recognized standard methods and recommendations from EMSD.

Acceptable limits of cooling water quality is included to help you to identify which parameter is not within standards.

We will not leave you alone after the testing. If you have further questions about the testing, please call or e-mail us and our staff will answer your questions promptly.