Monitoring of Cooling Tower Water
Cooling towers cools the warm water by direct contact between atmospheric air and the water. This process allows airborne contaminants, organic matters and particles to become deposited into the cooling water. This, combined with the contaminants in the feed water, creates an environment for microorganism growth, solid deposits and scaling. If Legionella bacteria is present in the system, there is a risk to spread the Legionnaires' disease (退伍軍人病) to human via the air conditioning system. Therefore, cooling tower water quality must be monitored in a regular basis to prevent destroying of the system and spreading of diseases to users.
Code of Practice in Hong Kong
In
Hong Kong, Code
of Practice for Water-cooled Air Conditioning Systems has been published by
the Electrical and Mechanical Services Department (EMSD), HKSAR Government.
According to the practice, the following parameters should be monitored
regularly to ensure the cooling tower water meets the requirements:
|
Parameter |
Cooling Water Quality
Criteria (Fresh Water Typed Tower) |
Minimum
Monitoring Frequency |
|
Heterotrophic
colony count (HPC) |
Less
than 100,000 cfu/mL |
Monthly |
|
Legionella
bacteria count |
Less
than 10 cfu/mL |
Monthly
/ Quarterly |
|
Conductivity |
Less
than 1500 μS/cm |
Monthly |
|
Total
dissolved solids |
Less
than 1500 mg/L |
Monthly |
|
Suspended
solids |
Less
than 180 mg/L |
Monthly |
|
Calcium
hardness |
Less
than 500 mg/L |
Monthly |
|
pH |
8
– 10 |
Monthly |
|
Total
alkalinity |
80
– 500 mg/L |
Quarterly |
|
Chloride
as mg/L Cl |
Less
than 200 mg/L |
Quarterly |
|
Sulphate
as mg/L SO4 |
Less
than 200 mg/L |
Quarterly |
|
Total
iron as mg/L Fe |
Less
than 1.0 mg/L |
Quarterly |
|
Total
Residual Chlorine |
Less
than 0.3 mg/L |
Monthly |
|
Biochemical
Oxygen Demand (BOD5) |
Refer
to EPD’s Technical Memorandum on Standards for Effluent Discharged into
Drainage and Sewerage Systems, Inland and Costal Waters |
Monthly |
|
Chemical
Oxygen Demand (COD) |
Ref:
Code of Practice for Water-cooled Air Conditioning Systems Part 2: Operation and
Maintenance of Cooling Towers (EMSD, HKSAR, Jan 2007)
Why choose Enviro Labs?
|
Enviro Labs holds HOKLAS accreditation* for all the above parameters. |
|
|
We provide high quality of testing services at reasonable price. |
|
All the analyses are conducted according to the international recognized standard methods and recommendations from EMSD. |
|
Acceptable limits of cooling water quality is included to help you to identify which parameter is not within standards. |
|
|
We will not leave you alone after the testing. If you have further questions about the testing, please call or e-mail us and our staff will answer your questions promptly. |